Model | Wartość znamionowa (A) | Wartość znamionowa zwarcia 480 V AC (kA) | Wartość znamionowa zwarcia 600 V AC (kA) | Bezpiecznik Ferraz | |
MCD5-0021B | 23 | 65 | 10 | AJT50 | A070URD30XXX0063 |
MCD5-0037B | 43 | 65 | 10 | AJT50 | A070URD30XXX0125 |
MCD5-0043B | 50 | 65 | 10 | AJT50 | A070URD30XXX0125 |
MCD5-0053B | 53 | 65 | 10 | AJT60 | A070URD30XXX0125 |
MCD5-0068B | 76 | 65 | 10 | AJT80 | A070URD30XXX0200 |
MCD5-0084B | 97 | 65 | 10 | AJT100 | A070URD30XXX0200 |
MCD5-0089B | 100 | 65 | 10 | AJT100 | A070URD30XXX0200 |
MCD5-0105B | 105 | 65 | 10 | AJT125 | A070URD30XXX0315 |
MCD5-0131B | 145 | 65 | 18 | AJT150 | A070URD30XXX0315 |
MCD5-0141B | 170 | 65 | 18 | AJT175 | A070URD30XXX0315 |
MCD5-0195B | 200 | 65 | 18 | AJT200 | A070URD30XXX0450 |
MCD5-0215B | 220 | 65 | 18 | AJT250 | A070URD30XXX0450 |
MCD5-0245C | 255 | 85 | 85 | AJT300 | A070URD30XXX0450 |
MCD5-0360C | 360 | 85 | 85 | AJT400 | A070URD33XXX0630 |
MCD5-0380C | 380 | 85 | 85 | AJT450 | A070URD33XXX0700 |
MCD5-0425B | 430 | 85 | 85 | AJT450 | A070URD33XXX0700 |
MCD5-0595C | 620 | 85 | 85 | A4BQ800 | A070URD33XXX1000 |
MCD5-0619C | 650 | 85 | 85 | A4BQ800 | A070URD33XXX1000 |
MCD5-0790C | 790 | 85 | 85 | A4BQ1200 | 070URD33XXX1400 |
MCD5-0927C | 930 | 85 | 85 | A4BQ1200 | A070URD33XXX1400 |
MCD5-1200C | 1200 | 100 | 100 | A4BQ1600 | A065URD33XXX1800 |
MCD5-1410C | 1410 | 100 | 100 | A4BQ2000 | A055URD33XXX2250 |
MCD5-1600C | 1600 | 100 | 100 | A4BQ2500 | A055URD33XXX2250 |
Softstart Danfoss - MCD 500
Instalacja softstartów Danfoss MCD 500
Bezpieczniki UL - znamiona zwarcia softstartu Danfoss MCD 500